Main page content
TPI 709A740 Combustion Gas Analyzer Kit with IR Printer is designed to provide rapid pump driven measurements, fuel selection at start-up, and an automatic default to the last used fuel type. The TPI 709A740 features combustion efficiency calculation, an integrated manometer with 0.001" H20 resolution, an integrated differential thermometer, data logging up to 50 readings, and an easy-to-read illuminated display.
Features
| Characteristics: | TPI 709A740 Combustion Gas Analyzer Kit with IR Printer |
| Integrated manometer with 0.001" H2O resolution | |
| Calculates combustion efficiency | |
| Rapid pump-driven response | |
| Analyzer does not shut down if 15 CO ppm is present for safety reasons | |
| Selectable fuels include: Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse |
|
| A740 IR printer creates hard copies of test results | |
| Integrated differential thermometer | |
| Data logs up to 50 readings | |
| Easy-to-read illuminated display | |
| Warranty: | Unit - 3 Years ; Sensors - 2 Years |
| Includes: | Main Instrument, Rubber boot, Soft Carrying Case, Flue Sampling Probe, In-Line Filter assembly, Temperature Probe, Mini Pump Filter, Exhaust Spigot, IR Printer, Owners Manual |
Specifications
| Specifications: | TPI 709A740 Combustion Analyzer Kit with IR Printer |
| Carbon Monoxide (CO) Measurement | |
| Range | 0 to 10,000 ppm |
| Resolution | 1 ppm |
| Accuracy | +/-5ppm or 5% of reading whichever is greater |
| Oxygen (02) Measurement | |
| Range | 0 to 25% |
| Resolution | 0.1% |
| Accuracy | ±0.3% |
| Carbon Dioxide (CO2) - Calculated Value | |
| Range | 0 to 25% |
| Resolution | 0.1% |
| Temperature Measurement | |
| Range | -40 to 1472°F, or -40 to 800°C |
| Resolution | 1° F or °C |
| Accuracy (K-type) | ±0.3%, ±2°F or ±1°C |
| Draft/Pressure Measurement | |
| Ranges | -150 mBar to +150 mBar -15 kPa to +15 kPa -60 inH2O to +60 in H20 |
| Resolution | 0.001 inH2O |
| Accuracy | ±0/5% fsd |
| Gross/Net Efficiency - Calculated Value | |
| Range | 0 to 100% |
| Resolution | 0.1% |
| Other | |
| Operating Temperature | 14°F to 122°F (-10°C to 50°C) |
| Battery Type | 1.5V AA (3) |
| Selectable Fuels | Natural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse |
| Display Type | Backlit 3 line LCD |
| Data Storage | 50 Locations |
| Print Capability | Yes, via optional IR printer (A740) |
| Date and Time Function | 24 Hour Real Time Clock |
| Dimensions | 200mm x 90mm x 60mm |
| Weight | 500g |
| Conformity | BS7927 (and the draft BS7967) |
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Resources
Video TPI 709A740 Combustion Gas Analyzer Kit with IR Printer https://youtu.be/XgtY8-POoyg