Main page content
AEMC PEL 105 Power Energy Data-Logger with Wireless Data Transfer AmpFlex 196A-24-BK sensors is a powerful energy and power data logger for single phase, dual phase, and three-phase systems. The PEL 105 measures power factor, amps, volts, kWh, watts, VARs, and harmonics out to the 50th with 4 current inputs and 5 voltage inputs. The PEL 105 is capable of communicating via Wi-Fi, Ethernet, Bluetooth, and USB connections for more user freedom and safety when using wireless connections.
The AEMC PEL 105 is designed for overall energy audits, system monitoring, upgrades, and incoming power monitoring, including compliance to article 220.87 of the NEC, and is an excellent tool for electricians, engineers and contractors. The PEL 105 includes the impressive DataView software for PC computers. The DataView software allows the user to configure functions and parameters, analyzes real time data, datalog, print templates, analyze graphs, and more. The DataView software is also available for Android devices as an App for data analysis and quick configuration.
AEMC’s PEL 105 measures neutral current, which is a feature not found on the less expensive power energy loggers. This feature is extremely helpful for making sure there is no voltage leakage into the neutral line. The PEL 105 powers directly from phase inputs up to 1000VAC, which is very helpful for when there are no power receptacles nearby.**Includes x4 water-tight AmpFlex® 196A-24-BK sensors**
Available PEL 105 without measurement sensors.
Features
| Characteristics: | AEMC PEL 105 Power Energy Data-Logger with Wireless Data Transfer AmpFlex 196A-24-BK sensors |
| Single-, dual- (split-phase), and three-phase power and energy loggers | |
| Works on 400Hz, 60Hz, or 50Hz networks | |
| Works in 1000V CAT IV environments | |
| Measures power: VA, W, and Var | |
| Measures energy: VAh, Wh (source, load), and varh (4 quadrants) | |
| Measures and records time of use costs | |
| Data storage, real-time display, analysis, and report generation with supplied pre-defined or custom templates with DataView Software | |
| DataView App is also available on Android for real time display and quick configuration options | |
| Wifi, ethernet, Bluetooth, and USB connections | |
| Requires little to no setup | |
| Bluetooth Class 1 is up to 300 ft when in direct line of site and unobstructed | |
| Satisfies the recommendations of NEC 220.87 | |
| Fully waterproof (IP67 rating) and designed for outdoor use | |
| Flexible current sensors are also waterproof (not included; available separately) | |
| Can be powered from phase inputs up to 1000 VAC | |
| Measures DC voltage from 10V to 1000 VDC | |
| Datalogs at 1 sec 200ms | |
| Capable of being mounted to a pole | |
| Measures current up to 10,000A AC (sensor dependent) | |
| Monitor stray voltages on neutral line | |
| Includes: | Includes x4 water-tight AmpFlex® 196A-24-BK sensors, Extra-large tool bag, accessory pouch, 5 ft USB cable, five 10 ft. black voltage leads (waterproof cap) with alligator clips, power adapter 110/230V with US power cord, 9.6V NiMH battery, 12 color-coded input ID markers, SD-card (8GB), USB SD-card reader, quick start user guide, and a USB stick supplied with DataView software and user manual |
| Warranty: | Limited 1 Year Warranty |
Specifications
| Specfications: | AEMC PEL 105 Power and Energy Logger Wireless with 4 Waterproof Sensors | ||
| Sampling Frequency | 128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz) | ||
| Data Storage Rate | 1 per second (200ms also available on PEL 105) | ||
| Demand Period Storage Rate | User selectable (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30 and 60 minutes) Recorded Parameters | ||
| Recorded Parameters (Single- and Poly-Phase) | V, I, W, VA, var, PF, Tan, Wh, VAh, varh, THD (V and I), Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF | ||
| Event Log | Tracks and records status changes and error messages along with recorded data | ||
| Front Panel Indicator LEDs | Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status | ||
| Storage Capactiy | SD card included / SD cards up to 32 GB formatted FAT32 are supported | ||
| Inputs Voltage | PEL 102/103: 4 input channels; PEL 105: 5 input channels via 4mm safety banana jacks | ||
| Current | PEL 102/103: 3 current input channels ; PEL 105: 4 input channels via custom 4 pin jacks that accept AEMC® probes and sensors | ||
| Electrical | |||
| Voltage Measurement | PEL 102/103 RANGE | PEL 105 RANGE | RESOLUTION/ACCURACY* |
| 50/60Hz | 42.5 to 69Hz | 42.5 to 69Hz | ±0.1Hz |
| Single-Phase RMS Voltages | 10 to 1000Vrms | 10 to 1000Vrms | 0.1V/±0.2% Rdg ± 0.2V |
| Phase-to-Phase RMS Voltages | 17 to 1700Vrms | 17 to 1000Vrms | 0.1 to 1V/±0.2% Rdg ± 0.4V |
| 400Hz | 340 to 460Hz | 340 to 460Hz | – |
| Single-Phase RMS Voltages | 10 to 600Vrms | 10 to 600Vrms | 0.1V/±1% Rdg ± 1V |
| Phase-to-Phase RMS Voltages | 17 to 1200Vrms | 17 to 600V | 0.1 to 1V/±1% Rdg ± 1V |
| DC | 100 to 1000V | 10 to 1000V | 0.1V/±1% Rdg ± 3V (typical) |
| PT Ratios | Programmable from 50 to 650,000V | - | 0.01 to 0.1V |
| Current Measurement | A193*** | 196A*** | - |
| Nominal range for current probes supplied with kit. See chart on pg 11 for other probes | 200mA to 3000Arms | 200mA to 10,000A | - |
| CT Ratios | Programmable from 1:1 to 25,000:1 (probe dependent) | ||
| Power Measurements | Range | Resolution | - |
| Active Power (P)* E= 1018 | -2 to 2GW | 0.001W | ±0.5% Rdg ± 0.005% Pnom |
| Reactive Power (Q)* | -2 to 2Gvar | 0.001var | ±1% Rdg ± 0.01% Qnom |
| Apparent Power (S)* | 0 to 2GVA | 0.001VA | ±0.5% Rdg ± 0.005% Snom |
| Power Factor | -1 to +1 | 0.001 | ± 0.05 |
| Tangent f (active/reactive power ratio) | -3.2 to +3.2 | 0.001 | ± 0.02 |
| Energy Measurements | |||
| Active Energy (EP) | 0 to 4 x 10"; 4Ewh | 1Wh | ±0.5% Rdg |
| Reactive Energy (EQ) | 0 to 4 x 10" ; 4Evarh | 1varh | ±2% Rdg |
| Apparent Energy (ES) | 0 to 4 x 10" ; 4EVAh | 1Vah | ±0.5% Rdg |
| THD | ± 655% | ||
| Individual Harmonics | 1 to 50 displayed in percentage; 1 to 7 at 400Hz External Supply | ||
| External Supply | 110V/250V (10%) @ 50/60Hz; 400Hz | ||
| Power From Phase Measurement | PEL 102/103: requires optional Power Adapter Cat #2137.77; PEL 105: 100V to 1000Vac | ||
| Back-Up Power Source/Charge Time | Rechargeable 8.4V NiMH battery pack / Approximately 5 hours | ||
| Battery Life | 30 minutes minimum, 60 minutes typical | ||
| Mechanical | |||
| Communication Ports | USB 2.0, Ethernet (RJ45), Wireless Bluetooth Class 1 **/ PEL 105 only: Wi-Fi | ||
| Dimension/Weight | PEL 102/103: 10.08 x 4.92 x 1.46" (256 x 125 x 37mm) / 2.20lbs (1kg); PEL 105: 10.6 x 7.1 x 9.65" (270 x 180 x 245mm) / 8.8lbs (4kg) | ||
| Case | PEL 102/103: Double insulated, rubber over-molded, polycarbonate UL94 V1 rated / PEL 105: Polycarbonate UL94 V1 rated | ||
| Mounting/Security | PEL 102/103: Kensington anti-theft system / Embedded magnets on back side, keyhole slot on back side | ||
| Display | |||
| Display Type | PEL 102/103: 2.63 x 2.16" (67 x 55mm), four line, monochrome, backlit LCD with adjustable brightness & contrast PEL 105: 4.2 x 3.3" (107 x 84mm), four line, monochrome, backlit LCD with adjustable brightness & contrast | ||
| Environmental / Safety | |||
| Operating Temperature/Relative Humidity | PEL 102/103: 50° to 122°F (10° to 50°C) / 45 to 75%RH; PEL 105: -4° to 122°F (-20° to 50°C) / 45 to 75%RH | ||
| Storage Temperature | PEL 102/103: -4° to 122°F (-20° to 50°C) with batteries; -4° to 158°F (-20° to 70°C without batteries) PEL 105: -40° to 95°F (-40° to 35°C from 0 to 95%HR); -40° to 158°F (-40° to 70°C from 0 to 75%HR) | ||
| Safety Rating / CE Rating | PEL 102/103: Complies with IEC 61010-1:Ed3, and IEC 61010-2-030:Ed1 for 1000V CAT III / 600V CAT IV, Pollution Degree 2 / PEL 105: 1000V CAT IV, Pollution Degree 4 (closed) / Yes | ||
| Index of Protection | PEL 102/103: IP54 non operating / PEL 105: IP67 with cover closed | ||
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Resources