Main page content
AEMC PEL 103 Advanced Power Energy Logger with Digital Display is an easy to use, economical, two (split phase) and three phase power/energy data logger. AEMC PEL 103 Advanced Power Energy Logger with Digital Display measures RMS voltages, currents, VA, W and var power values, VAh, Wh, and varh energy values and stores every second. DataView software is included for data retrieval, configuration and measurement analysis in real-time.
Features
| Characteristics: | AEMC PEL 103 Advanced Power Energy Logger with Digital Display |
| RMS voltages and currents are measured at 128 times per cycle and stored each second | |
| VA, W, and var power values are measured (total and per phase) and stored every second | |
| VAh, Wh, and varh energy values are measured (total and per phase) and stored every second | |
| Calculates the cos ? Displacement Power Factor (DPF) and the Power Factor (PF) stored every second | |
| Calculates Total Harmonic Distortion (THD) | |
| Harmonics up to the 50th order for 50/60 Hz and 7th order for 400Hz are measured, calculated and displayed | |
| DC quantities (RMS calculation) measured | |
| Measurements displayed | |
| A removable SD-card stores electrical network quantities | |
| Connected current sensors automatically recognized | |
| Includes DataView software for configuration, data retrieval and real-time viewing of measurements with a PC | |
| Small, durable case | |
| Built in, versatile communication interface choices built in (USB, Ethernet, Bluetooth) | |
| Now Available with an Android App - Go to the PEL Google play App page online to downloadthe FREE Android App |
Specifications
| Specifications | AEMC PEL 103 Power and Energy Logger | ||
| General | |||
| Sampling Frequency | 128 samples per cycle; 50/60Hz (16 samples/cycle 400Hz) | ||
| Data Storage Rate | 1 per second | ||
| Demand Period Storage Rate | User selectable (1,2,3,4,5,6,10,12,15,20,30 and 60 minutes) | ||
| Recorded Parameters (Single- and Poly-Phase) | V, I, W, VA, var, PF, Tan, Wh, Vah, varh, THD (V and I), Individual harmonics (from 1 through 50 per phase); Crest Factor (CF), Cos f / DPF | ||
| Event Log | Tracks and records status changes and error messages along with recorded data | ||
| Front Panel Indicator LEDs | Bluetooth active, recording in progress, phase connection reversal, overload, battery charging and SD Card status | ||
| Storage Capacity | 2GB SD card (included) is used for storage. SD cards (up to 2GB); SDHC cards (4 to 32GB) formatted FAT32 are supported | ||
| Input - Voltage | 3 voltage Input channels via 4mm safety banana jacks | ||
| Input - Current | 3 current Input channels via custom 4 pin jacks that accept AEMC probes and sensor | ||
| Electrical | |||
| Voltage Measurement | Range | Resolution | Accuracy (% of Reading)* |
| 50/60Hz | 42.5 to 69Hz | - | ± 0.1Hz |
| Single-Phase RMS Voltages | 100 to 1000rms | 0.1V | ± 0.2% Reading ± 0.2V |
| Phase-to-Phase RMS Voltages | 100 to 2000Vrms | 0.1 to 1V | ± 0.2% Reading ± 0.4V |
| 400Hz | 340 to 460Hz | - | - |
| Single-Phase RMS Voltages | 100 to 600Vrms | 0.1V | ± 1% Reading ± 1V |
| Phase-to-Phase RMS Voltages | 200 to 1200Vrms | 0.1 to 1V | ± 1% Reading ± 1 V |
| DC | 100 to 1000V | 0.1V | ± 1% Reading ± 3V (typical) |
| PT Ratios | Programmable from 50V to 65,000V | 0.01V to 0.1V | - |
| Current Measurement | |||
| Current Probe: MiniFlex Sensor MA193*** | 100mA to 100Arms 20 to 400Arms 100 to 2000Arms 500 to 10,000Arms | 1 to 100mA 10 to 100mA 0.1 to 1A 0.1 to 1A | ± 1% ± 50mA ± 1% ± 0.2A ± 1% ± 1A ± 1% |
| CT Ratios | Programmable from 1:1 to 25,000:1 (probe dependant) | ||
| Power Measurements | |||
| Active Power (P)* | -2 to 2GW | 0.001W | ± 0.5% Reading ± 0.005% Pnom |
| Reactive Power (Q)* | -2 to 2Gvar | 0.001var | ± 1% Reading ± 0.01% Qnom |
| Apparent Power (S)* | 0 to 2GVA | 0.001VA | ± 0.5% Reading ± 0.005% Snom |
| Power Factor | -1 to +1 | 0.001 | ± 0.05 |
| Tangent F (active/reactive power ratio) | -3.2 to +3.2 | 0.001 | ± 0.02 |
| Energy Measurements | |||
| Active Energy (EP) | 0 to 4x1018 | 1Wh | ± 0.5% Reading |
| Reactive Energy (EQ) | 0 to 4x1018 | 1varh | ± 2% Reading |
| Apparent Energy (ES) | 0 to 4x1018 | 1Vah | ± 0.5% Reading |
| THD | ± 655% | ||
| Individual Harmonics | 1 to 50 displayed in percentage; 1 to 7 at 400Hz | ||
| External Supply | 11V/250V (10%) @ 50/60Hz; 400Hz | ||
| Back-Up Power Source / Charge Time | Rechargeable 8.4V NIMH battery pack / Approximately 5 hours | ||
| Battery Life | Provides up to 30 minute ride through upon power loss | ||
| Mechanical | |||
| Communication Ports | USB 2.0, Ethernet (RJ45) Wireless Bluetooth Class 1 ** | ||
| Dimension / Weight | 10.08" x 4.92" x 1.46" (256 x 125 x 37mm) / < 2.2lbs (<1kg) | ||
| Case / Index of Protection | Double Insulated, rubber over-molded, polycarbonate UL94 V1 rated / IP54 non operating | ||
| Mounting / Security | Embedded magnets on back side, keyhole slot on back side / Kensington anti-theft system | ||
| Display | |||
| Display Type for Model PEL 103 | 2.63 x 2.16" (67 x 55mm), four line, monochrome, backlit LCD with adjustable brightness and contrast | ||
| Environmental / Safety | |||
| Operating Temperature/ Relative Humidity | 32° to 122°F (0° to 50°C) / up to 85% | ||
| Storage Temperature | -4° to 122°F (-20° to 50°C) with batteries; -4°C to 158°F (-20°C to 70°C without batteries) | ||
| Safety Rating / CE Rating | Complies with IEC 61010-1: Ed3, and IEC 61010-2-030:Ed1 for 1000V CAT III / 600V CAT IV, Pollution Degree 2 / Yes | ||
| * Maximum value is current probe dependant. | |||
| ** Computers with Class II Bluetooth will restrict range to 40ft. Computers without Bluetooth will require a Class I or Class II Bluetooth radio adapter. | |||
| *** Maximum current reduced by a factor of 2 for 400Hz fundamental frequency. | |||
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Resources
Data Sheets

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Brochure.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Data Sheet.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Data Sheet (Español).pdf
Manuals

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Manuals.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Manual (Français).pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Manual (Español).pdf
Quick Guides

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Quick Guide.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Quick Guide (Français).pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Quick Guide (Español).pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Brochure.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Data Sheet.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Data Sheet (Español).pdf
Manuals

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Manuals.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Manual (Français).pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Manual (Español).pdf
Quick Guides

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Quick Guide.pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Quick Guide (Français).pdf

AEMC PEL 103 Advanced Power Energy Logger with Digital Display - Quick Guide (Español).pdf
AEMC PEL 103 Advanced Power Energy Logger with Digital Display