Main page content
The AEMC 6555 Portable Digital Megohmmeter is a fully automated 15,000V graphical insulation tester. Features the ability to set up three step voltage profiles (40V to 15,000V), each including up to ten steps. Also includes three ramp profiles and three programmable test voltages in addition to the default set voltages of 500V, 1000V, 2500V, 5000V, 10,000V, and 15,000V. Fully compatible with PC.
Features
| Chracteristics: | AEMC 6555 Portable Digital Megohmmeter |
| Detects and measures frequency, input voltage, and current prior to testing | |
| Test Voltage range: 15,000VDC, 10,000, 5000, 2500, 1000, 500 | |
| Measures ramp voltage from 40V to 1100V or 500V to 15,000V | |
| Measures step voltage from 40V to 15,000V | |
| Non-destructive test, tests stop at preset current or Burn mode with no preset | |
| Insulation measurements digitally filtered | |
| Live voltage measurement to warn user | |
| Adjustable thresholds to trigger audible alarms | |
| Timed measurement checks | |
| Fuse protection feature | |
| Data logs up to 80,000 measurements | |
| PC compatible via USB | |
| Dust & Water Resistant when case is closed (IP54) |
Specifications
| Specifications | AEMC 6555 Megohmmeter | |
| Test Voltage | 500V 1,000V 2,500V 5,000V 10,000V 15,000V | 10kΩ to 2,000GΩ (2TΩ) 10kΩ to 4,000GΩ (4TΩ) 10kΩ to 10,000GΩ (10TΩ) 10kΩ to 15,000GΩ (15TΩ) 10kΩ to 25,000GΩ (25TΩ) 10kΩ to 30,000GΩ (30TΩ) |
| Fixed Test Voltages | 500/1,000/2,500/5,000/10,000/15,000V | |
| Variable Voltages | Variable: 40V to 15kV ; Three user programmable voltage schemes | |
| Ramp Mode | Programmable ramps ; start voltage / end voltage / duration | |
| Ramp Configuration Range | 40 to 1100V / 500 to 15,000V | |
| Step Mode | Up to 10 steps (voltage and duration configurable for each step) | |
| Voltage Measurement After Test | 0 to 2500VAC ; 0 to 4000VDC | |
| Capacitance Measurement | 0.005 to 9.999μF / 10.00 to 49.99μF | |
| Leakage Current Measurement | 0 to 8mA | |
| Discharge After Test | Yes / Automatic | |
| Additional Test Stop Modes | I-Limit Early-Break Timer | Programmable: 0.2 to 5mA di/dt Up to 99 minutes 59 seconds |
| Burn Mode | Constant Testing | |
| Ratio Calculation | PI, DAR, DD | |
| Calculation of R at ref. T° | Yes | |
| Measurement Display Filter | 3 filters with 3 possible time-constants | |
| Graphs on Display | R(t)+V(t); I(t); I(V) | |
| Storage | 256 registers, stores 80,000 points: R, V, I and date | |
| Communication | USB optically-isolated port | |
| PC Software | DataView | |
| Power Supply | NiMH rechargeable batteries, two 9.6V 4Ah battery packs charging by external voltage; 90 to 260V; 50/60Hz | |
| Battery Charging | Battery charging allowed while performing insulation measurements | |
| Electrical Safety | 1000V CAT IV; IEC61010-1 and IEC 61557 | |
| EMC, Mechanical Protection, Altitude | EN 61326-1, IP54, 3000m | |
| Dimensions / Weight | 13..39" x 11.81" x 7.87" (340 x 300 x 200mm) ; approx 13.64lbs (6.2kg) (excluding accessories) | |