Main page content
The AEMC 6417 Clamp-On Ground Resistance Meter is capable of measuring ground rod and grid impedance and resistance without the need for auxiliary rods. Can be used on multi-grounded systems without de-energizing or disconnecting the ground system being tested. Clamps around conductor or grounding electrode to measure the resistance to ground. Confirms the quality of grounding connections and bonds when performing measurements on intact ground systems. Also capable of measuring continuity and resistance of grounding loops around buildings and pads.
Features
| Characteristics: | AEMC 6417 Clamp-On Ground Resistance Meter |
| Uses contact voltage indication to alert user of unsafe conditions | |
| Ample yellow OLED display | |
| Selectable test frequency allows improved accuracy in inductive environments | |
| Distinguishes between ground resistance and loop measurements | |
| 35mm Jaw accommodation | |
| Data logs up to 2000 measurements with timestamps | |
| Automatic Shut-off Feature | |
| Rapid field checks for amps, ohms, and volts with an adjustable buzzer alert | |
| Heavy duty design | |
| Class 2 Bluetooth with PC and Android support | |
| DataView software with report generation, system configuration, data storage, real-time display, and analysis. | |
| Includes: User's manual, hard carrying case, calibration loop, four 1.5V AA batteries, Bluetooth USB adapter, quick start guide, and a USB stick with DataView software |
Specifications
| Specifications: | AEMC 6417 Ground Resistance Tester Clamp-On | ||
| Ground Resistance Auto-Ranging 1 to 199O | Measurement Range | Resolution | Accuracy (% of Reading) |
| 0.010 to 0.099O | 0.001O | ±1.5% ±0.01O | |
| 0.10 to 0.99O | 0.01O | ±1.5% ±0.01O | |
| 1.0 to 49.9O | 0.1O | ±1.5% ±0.1O | |
| 50.0 to 99.5O | 0.5O | ±2% ±0.5O | |
| 100 to 199O | 1O | ±3% ±1O | |
| 200 to 395O | 5O | ±5% ±5O | |
| 400 to 590O | 10O | ±10% ±10O | |
| 600 to 1150O | 50O | 20% approx | |
| 1200 to 1500O | 50O | 25% approx | |
| Current Measurement Auto-Ranging 1mA to 40A | 0.200 to 0.999mA | 1µA | ±2% ±50µA |
| 1.000 to 2.990mA 3.00 to 9.99mA | 10µA | ±2% ±50µA | |
| 10.00 to 29.90mA 30.0 to 99.9mA | 100µA | ±2% ±100µA | |
| 100.0 to 299.0mA 0.300 to 0.990A | 1mA | ±2% ±1mA | |
| 1.000 to 2.990A 3.00 to 39.99A | 10mA | ±2% ±10mA | |
| Resistance Measurement Frequency | 2083Hz | ||
| Current Measurement Frequency | 47 to 800Hz | ||
| Loop Impedance Measurement | 10 to 100µH; 100 to 500µH | ||
| Current Overload | OL displayed above 39.99Arms | ||
| Communication | Bluetooth connection | ||
| Power Source | 4x1.5V LR6 (AA) Alkaline batteries or 4 NiMH batteries; Battery life: 12 hours, or 1440 30-second measurements approx. | ||
Proposition 65 Warning for California Residents: This product can expose you to chemicals including Benzene, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.
Resources
Data Sheets
AEMC 6417 Clamp-On Ground Resistance Meter - Brochure.pdf
AEMC 6417 Clamp-On Ground Resistance Meter - Series Brochure.pdf
AEMC 6417 Clamp-On Ground Resistance Meter - Data Sheet.pdf
AEMC 6417 Clamp-On Ground Resistance Meter - Selection Chart.pdf
Manuals
AEMC 6417 Clamp-On Ground Resistance Meter - Manual.pdf
AEMC 6417 Clamp-On Ground Resistance Meter - Manual (Français).pdf
AEMC 6417 Clamp-On Ground Resistance Meter - Manual (Español).pdf
AEMC 6417 Clamp-On Ground Resistance Meter - Quick Start.pdf
Manuals
AEMC® - 6416 & 6417 Clamp-On Ground Tester - Introduction
AEMC® - 6416 6417 with OLED Display
AEMC® - 6416-6417 Clamp On - Loop Alarm