| Datasheet: |
 |
| Wohler A 600 Combustion Emissions Analyzer Wohler 6105 Description: |
 Wohler A 600 Professional Combustion Emissions Analyzer 6105 PC-Complete Set is the next generation of commercial and industrial combustion and emission analysis. Rely on latest technology with approved touch screen operational concept and wireless bluetooth probe. Free ground shipping within continental US.
 |
| Wohler A 600 Combustion Emissions Analyzer Wohler 6105 Characteristics: |
| |
 Wireless probe for versatile applications
 |
| |
 Large full colour display - user selectable display readings with up to 12 readings and calculated data
 |
| |
 Patented Infrared-Touch-Screen
 |
| |
 Core temperature search with displayed graph
 |
| |
 Rapid Readout Technology (RRT)
 |
| |
 User adjustable fuel parameters
 |
| |
 Full automatic calibration
 |
| |
 Automatic CO-safety-valve
 |
| |
 Self-monitoring filter and pump
 |
| |
 Enhanced self diagnosis
 |
| |
 Field replaceable sensors
 |
| |
 6 filter technology
 |
| |
 More than 10 hours operation time with standard AA rechargeables
 |
| |
 Optional use of non-rechargeable standard AA batteries
 |
| |
 For more than 1,000 Measurement records on a SD/MMC memory card
 |
| |
 Infrared printer port
 |
| |
 Bluetooth link to computer or laptop
 |
| |
 USB interface
 |
| Wohler A 600 includes: |
 Wohler A 600 PC-Version complete set, Bluetooth probe, with O2 and CO 4,000ppm, NO, NO2, and SO2 sensor, hose, cone, air temperature probe, rechargeable batteries and power supply, multi hole CO probe, USB to Bluetooth adaptor, wading filters (1 pack), water stop filters (3 pcs)
 |
| Wohler A 600 Combustion Emissions Analyzer Wohler 6105 Features: |
| |
 Multiple fuels: oil, gas and solid fuel fired heat appliances
 |
| |
 Sensors: O2, CO 4,000 (standard), CO 100,000, NO, NO2, SO2, H2
 |
| |
 Variety of probes for different measurement tasks
 |
| |
 Adaptors for temperature and air flow probes
 |
| |
 Optional Peltier-Cooler and solid fuel adapter
 |
| |
 Customer adjustable fuel parameters
 |
| Wohler A 600 Combustion Emissions Analyzer Wohler 6105 Specifications: |
| Oxygen Concentration (O2): |
 Range: 0…21.0 Vol.%; Accuracy: ± 0.3 Vol.%
 |
| Carbon Monoxid Concentration (COlow): |
 Range: 0…4,000 Vol.ppm;
Accuracy: ± 20 ppm: (< 400 ppm), otherwise 5 % of reading
 |
| Hydrogen Concentration (H2): |
 Range: 0…1,000 Vol.ppm;
Accuracy: ± 40 ppm (<400 ppm), otherwise 10 % of reading
 |
| Carbon Monoxid Concentration (COhigh) (Opt): |
 Range: 0…100,000 Vol.ppm;
Accuracy: ± 100 Vol.ppm, (< 1,000 ppm),10 % of reading
 |
| Nitrogen Concentration (NOV) (Opt): |
 Range: 0…2,000 Vol.ppm, (permanent up to 1,000 ppm);
Accuracy: ± 5 ppm (< 400 ppm), otherwise 5 % of reading
 |
| Draft / Differential Pressure (PD): |
 Range: ± 150 hPa; Accuracy: ± 3.0 Pa (< 100,0 Pa), otherwise 3 % of reading; Resolution: 0.1 Pa
 |
| Air Temperature (TL): |
 Range: -4.0…212.0 °F; Accuracy: ± 2 °F
 |
| Flue Gas Temperature (TA): |
 Range: 14.0…1652.0 °F;
Accuracy: EN 50379, Part 2
 |
| CO2 Calculation: |
 Range: 0…CO2max; Resolution: 0.1 %
 |
| Stack Losses QA: |
 In reference to the selected fuel (Siegert formula)
Efficiency - η: Range:0…100.0 %, condensation is automatically detected;
Accuracy: 0.1 %
 |
| Dew Point Temperature: |
 Resolution: 0.2 °F, in reference to selected fuel
 |
| Condensate: |
 Readings in kg/m3 (gas) or kg/l (oil)
 |
| Air Speed: |
 Range:0.4 - approx. 130 m/s; Resolution: < 0.4 m/s
 |
| Air Flow: |
 Range: 0- 2,000 m3/h; Resolution: approx. 1 m3/h
 |
| Date/time: |
 Realtime clock with backup battery
 |
| Storage Temperature: |
 -4…122 °F
 |
| Working Temperature: |
 Range: 41 - 104 °F
for specified accuracies
 |
| Power Supply Hand Held: |
 6 x AA rechargeable batteries or mains supply
 |
| Power Supply Wireless Probe: |
 3 x AA rechargeable batteries or mains supply
 |
| Weight: |
 Approx. 2.65 lb.
 |
| Size: |
 9.5" x 6.1" x 2.5"(with docked probe)
 |