Datasheet: TPI-715 |
 |
| TPI 715 Combustion Analyzer Description: |
 TPI 715 Combustion Analyzer. All TPI analyzers feature quick and simple set up. Fast purge and the ability to perform fuel selection during start up enable tests to be performed quickly without requiring extra set-up time after initial startup.

TPI 715 Combustion Analyzer also uses the last selected fuel as the default setting. This feature prevents the need to perform fuel
selection every time the analyzer is turned on.

The TPI 715 Combustion Analyzer contents: 715 Combustion Analyzer; A787 Soft Carrying Case; A770 Flue Probe; A763 Mini pump; GK11M K-type thermocouple.

Use the optional A784 flow regulator to reduce the flow rate of the gas being sampled to measurable levels on high pressure systems such as gas compression engines. The A784 is included in the 715K3 kit. Free ground shipping within continental US.
 |
| TPI 715 Combustion Analyzer Applications: |
| |
 Tune combustion engines
 |
| |
 Test CO levels in industrial boilers
 |
| |
 Measure NO and calculate NOX
 |
| TPI 715 Combustion Analyzer Characteristics: |
| |
 Measure up to 9.999 percent CO
 |
| |
 Built-in differential thermometer
 |
| |
 Measure NO (Nitric Oxide), Calculate NOx
 |
| |
 Store function to save up to 10 readings
 |
| |
 Calculates combustion efficiency
 |
| |
 Pump driven for fast response
 |
| |
 Push on fittings for fast and easy use
 |
| |
 Large easy to read backlit display
 |
| |
 Will not shut off if 15 ppm CO is present for increased safety
 |
| |
 Ten selectable fuels
 |
| |
 Optional A740 IR printer available for hard copies of test results
 |
| 715 Contents: |

 |
| |
 715 Combustion Analyzer
 |
| |
 A787 Soft Carrying Case
 |
| |
 A770 Flue Probe
 |
| |
 A763 Mini pump
 |
| |
 GK11M K-type thermocouple
 |
| TPI 715 Combustion Analyzer Specifications: |
| Instrument |

 |
| Operating Temperature Range |
 14 degrees F to +122 degrees F (-10 degrees C to +50 degrees C)
 |
| Battery / Battery Life |
 AA (3) / > 6 Hours
 |
| Charger Input Voltage |
 12VDC (Cigarette ligher adapter incl.)
 |
| Fuels |
 Natural Gas, LPG, Light Oil, Heavy
Bituminous Coal, Anthracite Coal,
Coke, Butane, Wood, Bagasse
 |
| Units of Pressure |
 Mbar, kPa & inH2O
 |
| Display |
 3 Line Backlit LCD w/ annunciators
 |
| Data Storage |
 10 sets of readings
 |
| Data Logging |
 400 sets of readings
 |
| Single Logging |
 150 sets of readings
 |
| Time & Date |
 24 Hour Real Time Clock
 |
| Dimensions |
 7.8 inch x 3.5 inch x 2.4 inch
 |
| Weight |
 1.1lbs
 |
| Gases |

 |
| Oxygen |

 |
| Range |
 0-25 percent
 |
| Resolution |
 0.1 percent
 |
| Accuracy |
 +/- 0.3 percent
 |
| Carbon Monoxide |

 |
| Range |
 0-9.999 percent
 |
| Resolution |
 0.001 percent
 |
| Accuracy |
 +/- 5 ppm or 5 percent
 |
| Nitric Oxide |

 |
| Range |
 0-5,000ppm
 |
| Resolution |
 1 ppm
 |
| Accuracy |
 +/- 5 ppm to 5 percent
 |
| Carbon Dioxide |

 |
| Accuracy |
 Calculated
 |
| CO/CO2 Ratio |

 |
| Range |
 0-0.999
 |
| Resolution |
 0.001
 |
| Combustion Eff. |

 |
| Range |
 0-100 percent
 |
| Pressure Measurement |

 |
| Selectable Ranges |
 Mbar, kPa and inH2O
 |
| Range |
 -120 inH2O to 120 inH2O
 |
| Resolution |
 0.001 inH2O
 |
| Accuracy |
 +/- 0.5 percent fsd
 |
| Temperature Measurement |

 |
| Input Type |
 K-Type thermocouple
 |
| Range |
 -58 degrees F to 1832 degrees F (-50 degrees C to 1000 degrees C)
 |
| Resolution |
 1 degrees F (1 degrees C)
 |
| Accuracy |
 +/- (0.3 percent of rdg + 2 degrees F) or +/- (0.3 percent of rdg + 1 degrees C)
 |