| Datasheet: |
 |
| Ideal Industries 61-806 Power Quality Analyzer Description: |
 Ideal Industries 61-806 Power Quality Analyzer measures power factor, harmonics, energy and
works with one or three phase systems.

Ideal 61-806 is a great meter for power demand and more advanced studies of commercial and industrial work places.

Power quality analysis saves your money and protects your employees.
 |
| Ideal Industries 61-806 Power Quality Analyzer Characteristics: |
| |
 Single or three-phase measurements
 |
| |
 True RMS
 |
| |
 Data logging (1 MB memory)
 |
| |
 Auto ranging
 |
| |
 Min/max/avg
 |
| |
 Energy and Harmonics: Kilowatts, Voltamperes, Inductive reactive power, Capacitive reactive power, Power factor, Frequency, Kilowatt hour, Reactive power per hour, Total harmonic distortion, Harmonic factorization to 51st harmonic
 |
| |
 PowerVision Software
 |
| |
 Optional programs
 |
| |
 Lightweight portable design
 |
| |
 Easy-to-use push button operation
 |
| |
 Password protected on-screen setup
 |
| |
 RS-232 interface
 |
| |
 Customized data collection
 |
| |
 Real-time clock
 |
| |
 Programmable trigger-points and start/stop time
 |
| Warranty: |
 Lifetime limited warranty
 |
| |
 Backlight
 |
| |
 Neutral current capabilities
 |
| |
 Auto-detect clamps
 |
| |
 Optional FIFO memory
 |
| Ideal Industries 61-806 Power Quality Analyzer Specifications: |
| Supply voltage |
 Through an external power supplier set 120 VAC (+10% / -15%)
 |
| Frequency |
 50...60 Hz
 |
| Burden |
 8 VA
 |
| Operation temperature |
 0 - 50 șC
 |
| Measuring circuit |
 THREE PHASE, ARON
 |
| Safety |
 Category II - 600 V, as per EN 61010
 |
| Voltage measurement |
 Measuring range: 20 to 500 V a.c. (phase-neutral)
20 to 866 V a.c. (between phases) automatic scale adjustment
Other voltages: through suitable voltage transformers
Frequency: 45 to 65 Hz
 |
| Current measurement |
 Measuring range: see available current clamps
Current transducer ratio: user-programmable
Measurement units: automatic scale adjustment
 |
| Built-in clock |
 Date and time
 |
| Display |
 LCD; 160 x 160 pixels
 |
| RS-232 output |
 Serial type output
 |
| Internal memory |
 256 kbytes or 1 Mb according to the model
 |
| Accuracy |
 Voltage: 0.5 % of readout ± 2 digits
Current 0.5 % of readout ± 2 digits
Active power 1.0 % of readout ± 2 digits
Reactive power 1.0 % of readout ± 2 digits
 |
| Accuracy conditions |
 - Errors due to voltage and current transformer not included
- Temperature range: 5 șC to 45 șC
- Power factor: 0.5 to 1
- Measuring rang: between 5 % and 100 %
 |
| Case |
 Portable case
 |
| Dimensions |
 220 x 60 x 130 mm
 |
| Connection terminals |
 Input/output terminals
 |
| Keyboard/ display |
 In frontal panel
 |
| Weight |
 0,8 kg
 |
| Safety Standards |
 EN 60664,EN 610110, EN 61036, VDE 110, UL 94
 |

Need Technical Advise? Please Call: 602-795-4033