Datasheet: Fluke-116 |
 |
| Fluke hvac Multimeter 116 True RMS Description: |
 Fluke 116 hvac True RMS Multimeter (Mfg part No. 2538803) has everything needed in an HVAC meter including temperature and microamp measurements to quickly troubleshoot problems with HVAC equipment and flame sensors. This HVAC True RMS multimeter features low input impedance that helps prevent false readings due to ghost voltage.
 |
| Fluke hvac Multimeter 116 True RMS Applications: |
| |
 HVAC (heating ventilation air conditioning)
 |
| Fluke hvac Multimeter 116 True RMS Characteristics: |
| Virtual Product Demo |
 Clamp Meter Demo
 |
| |
 Built-in thermometer for HVAC applications
 |
| |
 Microamps to test flame sensors
 |
| |
 Low input impedance: helps prevent false readings due to ghost voltage
 |
| |
 Large white LED backlight to work in poorly lit areas
 |
| |
 Resistance, continuity, frequency and capacitance
 |
| |
 Min/Max/Average with elapsed time to record signal fluctuations
 |
| |
 Compact ergonomic design for one-handed operation
 |
| |
 Compatible with optional magnetic hanger (ToolPak™)
 |
| |
 CAT III 600 V safety rated
 |
| Warranty: |
 Three year warranty
 |
| Fluke hvac Multimeter 116 True RMS Specifications: |
| Maximum voltage between any terminal and earth gro |
 600 V
 |
| Surge protection |
 6 kV peak per IEC 61010-1 600 V CAT III, Pollution Degree 2
 |
| Display |
 Digital: 6,000 counts, updates 4 per second
 |
| Bar graph |
 33 segments, updates 32 per second
 |
| Operating Temperature |
 -10 °C to + 50 °C
 |
| Storage Temperature |
 -40 °C to + 60 °C
 |
| Battery type |
 Battery type 9 volt Alkaline, NEDA 1604A/ IEC 6LR61
 |
| Battery Life |
 400 hours typical, without backlight
 |
| Size |
 167 x 84 x 46 mm (6.57" x 3.31" x 1.82")
 |
| Weight |
 550 g
 |
| DC millivolts |
 Range: 600.0 mV
Resolution: 0.1 mV
Accuracy: +/-([% of reading] + [counts]): 0.5% + 2
 |
| DC volts |
 Range/Resolution: 6.000 V / 0.001 V
Range/Resolution: 60.00 V / 0.01 V
Range/Resolution: 600.00 V / 0.1 V
Accuracy: +/-([% of reading] + [counts]): 0.5% + 2
 |
| Auto volts |
 Range: 600.0 V
Resolution: 0.1 V
Accuracy: 2.0 % + 3 (dc, 45 Hz to 500 Hz)
4.0 % + 3 (500 Hz to 1 kHz)
 |
| AC millivolts true-rms |
 Range: 600.0 mV
Resolution: 0.1 mV
Accuracy: 1.0 % + 3 (dc, 45 Hz to 500 Hz)
2.0 % + 3 (500 Hz to 1 kHz)
 |
| AC volts true-rms |
 Range/Resolution: 6.000 V / 0.001 V
Range/Resolution: 60.00 V / 0.01 V
Range/Resolution: 600.0 V / 0.1 V
Accuracy: 1.0 % + 3 (dc, 45 Hz to 500 Hz)
2.0 % + 3 (500 Hz to 1 kHz)
 |
| Continuity |
 Range: 600 Ω
Resolution: 1 Ω
Accuracy: Beeper on < 20 Ω, off > 250 Ω; detects opens or shorts of 500 μs or longer.
 |
| Ohms |
 Range/Resolution: 600.0 Ω / 0.1 Ω
Range/Resolution: 6.000 kΩ / 0.001 kΩ
Range/Resolution: 60.00 kΩ / 0.01 kΩ
Range/Resolution: 600.0 kΩ / 0.1 kΩ
Range/Resolution: 6.000 MΩ / 0.001 MΩ
Accuracy: 0.9 % + 1
Range/Resolution: 40.00 MΩ / 0.01 MΩ
Accuracy: 1.5 % + 2
 |
| Diode Test |
 Range/Resolution: 2.000 V / 0.001 V
Accuracy: 0.9% + 2
 |
| Capacitance |
 Range/Resolution: 1000 nF / 1 nF
Range/Resolution: 10.00 μF / 0.01 μF
Range/Resolution: 100.0 μF / 0.1 μF
Range/Resolution: 9999 μF / 1 μF
Range/Resolution: 100 μF to 1000 μF
Accuracy: 1.9% + 2
Range/Resolution: > 1000 μF
Accuracy: 5% + 20%
 |
| LoZ capacitance |
 Range: 1 nF to 500 μF
Accuracy: 10% + 2 typical
 |
| Temperature (Type-K thermocouple) |
 Range/Resolution: -40 °C to 400 °C / 0.1 °C
Accuracy: 1% + 102
Range/Resolution: -40 to 752 °C / 0.2 °F
Accuracy: 1% + 182
 |
| AC μamps true-rms (45 Hz to 500 Hz) |
 Range/Resolution: 600.0 μA / 0.1 μA
Accuracy: 1.0% + 2
 |
| DC μamps |
 Range/Resolution: 600.0 μA / 0.1 μA
Accuracy: 1.0% + 2
 |
| Hz (V or A input) |
 Range/Resolution: 99.99 Hz / 0.01 Hz
Range/Resolution: 999.99 Hz / 0.1 Hz
Range/Resolution: 9.999 Hz / 0.001 Hz
Range/Resolution: 50.00 Hz / 0.01 Hz
Accuracy: 0.1% + 2
 |

Need Technical Advise? Please Call: 602-795-4033