Datasheet: E-Instruments-BTU-1100 |
 |
| E Instruments BTU 1100-1 Combustion Analyzer Description: |
 E Instruments BTU 1100-1 Combustion Analyzer is designed to maximum your combustion efficiency, easily set-up, install, and properly service any residential and/or light commercial boilers and burners.

E Instruments BTU 1100-1 Combustion Analyzer measure, display and print combustion efficiency, O2, CO, CO2, along with ALL of the necessary temperature, draft, and pressure measurements. Made in Italy. Free ground shipping within continental US.
 |
| E Instruments BTU 1100-1 Combustion Analyzer Applications: |
| |
 Designed to service residential and light commercial boilers and burners.
 |
| E Instruments BTU 1100-1 Combustion Analyzer Characteristics: |
| Includes: |
 Built-in impact printer, Dual Hose (Gas and Draft Measurements Simultaneously), 12" Probe, Vinyl Carrying Case with Shoulder Strap and Protective, Magnetic Rubber Boot
 |
| Measures: |
 O2, CO, CO2, Efficiency, Excess Air, Ambient and Flue Gas Temperture (Tair, Tgas), Draft and Differential Pressure, Ambient CO Monitoring and 10 Different Fuels and Oils (user-defined)
 |
| |
 Economical, Ergonomic, Compact, and Rugged
 |
| |
 Easy to use with direct function keys
 |
| |
 Rechargeable Battery with AC Charger Included (standard)
 |
| |
 Large 4-Line LCD (with automatic backlight)
 |
| |
 Real Time Clock with Date and Time
 |
| |
 CO with 1 ppm resolution
 |
| |
 Proprietary Design Water Trap (patent-pending)
 |
| |
 IR Output to use your old HP Thermal Printer
 |
| |
 Tc type K mini-DIN connector for any temperature probe
 |
| |
 Ready for the future with Upgradebale Internal Software on Flash Memory
 |
| |
 Settings can be display in the following languages: English, Spanish, French, Portugese, Italian, and other European languages
 |
| E Instruments BTU 1100-1 Combustion Analyzer Specifications: |
| O2: |
 Sensor: Electrochemical
Range: 0 - 25%
Resolution: 0.1%
Accuracy: ±0.2% vol
 |
| CO (H2 Compensated w/ Built-in NOX Filter: |
 Sensor: Electrochemical
Range: 0 - 8000 ppm
Resolution: 1 ppm
Accuracy: ±20 ppm <400ppm
±5% rdg up to 2000 ppm
±10% rdg for >2000 ppm
 |
| CO2: |
 Sensor: Calculated
Range: 0 - 99.9%
Resolution: 0.1%
 |
| Tair: |
 Sensor: Pt100
Range: -10 to 212°F
Resolution: 0.1°F
Accuracy: ± 1°F
 |
| Tgas: |
 Sensor: Tc K
Range: -10 to 1830°F
Resolution: 0.1°F
Accuracy: ± 2°F
 |
| Differential Temp.: |
 Sensor: Calculated
Range: -10 to 1830°F
Resolution: 0.1°F
 |
| Pressure/Draft: |
 Sensor: Semiconductor
Range: + 0 - 40 inH2O
Resolution: 0.001 inH2O
Accuracy: ±0.008 inH2O for ±0.16 inH2O ± 5% meas. val. elsewhere
 |
| Excess Air: |
 Sensor: Calculated
Range: 1.00 - infinity
Resolution: 0.01
 |
| Efficiency: |
 Sensor: Calculated
Range: 0-100%
Resolution: 0.1% (also for condensing boilers with automatic detection)
 |

Need Technical Advise? Please Call: 602-795-4033