Datasheet: DM-4 |
 |
| Amprobe DM-4 Power Quality Recorder Analyzer Description: |
 Amprobe DM-4 Power Quality Recorder Analyzer is the newest tester that addresses the needs of the most demanding Power Quality professionals.

Amprobe DM 4 incorporates full set of measuring features crucial for complete Power Quality analysis.

An innovative Remote User interface (PDA) allows safe, easy and convenient operation of the device remotely.

The Remote User Interface (PDA) is also used for data viewing, analysis and transfer.

Independently, the Amprobe DM4 can be used directly with the PC type of computer.

Since the DM-4 does not have any control buttons on its enclosure, it is protected against setup changes by unauthorized persons while the device is recording.
 |
| Amprobe DM-4 Power Quality Recorder Analyzer Characteristics: |
| |
 True RMS (TRMS)
 |
| |
 Extremely easy to setup and operate
 |
| |
 Comes as a complete kit: carrying case, CTs, test leads, PC
software & download cable, Remote User Interface (PDA) w/ protective
hard case and interface cable are included with product
 |
| |
 Rugged Remote User Interface with memory for easy data
downloads in the field and increased safety
 |
| |
 Works with single (two and three wire) and three phase
systems (Y and Delta)
 |
| |
 Detects and records voltage spikes 100 nS or slower
 |
| |
 Detects and records voltage Sags and Surges
 |
| |
 Built in scope displays waveforms
 |
| |
 Records all parameters (single or three phase) simultaneously
 |
| |
 Manual and programmable recording start
 |
| |
 Selectable fundamental frequency of 50 or 60 Hz
 |
| |
 Special data compression system and user selectable rates allow
recording from several hours to several years
 |
| |
 Download capabilities with PC (Windows compatible software) or
PDA (Palm OS)
 |
| |
 Line or battery powered
 |
| Amprobe DM-4 Power Quality Recorder Analyzer Features: |
| Safety: |
 CATIII, 600V
 |
| Supplied Current Transducer: |
 1000A Standard CT, 2” internal diameter CT
 |
| AC Current: |
 Standard CT (DM-CT-HTA): 5 - 1000A or optional Small size CT (DM-CT-100): 1A – 100A
 |
| Accuracy: |
 Input accuracy: +/-(2% Rdg + 2 LSD)
 |
| AC Voltage including Sags and Surges: |
 From 20V – to 1000V
Accuracy: +/-(3% Rdg + 2 LSD)
 |
| Voltage Transients: |
 200-6000Vpp; Duration > 100nS
 |
| Accuracy: |
 ±10% Rdg
 |
| Harmonics (Voltage and Current): |
 THD, DC and individual up to 51th
 |
| Accuracy: |
 +/-(5% Rdg + 2 LSD) @ DC to 25 harmonics**
 |
| Power: |
 Working (W), Reactive (VAR) and Apparent (VA)
 |
| Accuracy: |
 +/-(3.0% Rdg + 2 LSD)
 |
| Energy: |
 Working (kWh), Reactive (VARh) and Apparent (VAh)
 |
| Peak Demand: |
 KW
 |
| Power Factor (True and Displacement): |
 0.00 – 1.00
 |
| Accuracy: |
 +/-3%
 |
| Phase sequence: |
 1 - 2 – 3
 |
| Selectable Fundamental Frequencies: |
 50/60 Hz
 |
| Available Recording Time: |
 Several hours to several years depending on setup
 |
| Amprobe DM-4 Power Quality Recorder Analyzer Specifications: |
| 13.1.7 Temperature Drift |
 Temperature drift: 0.1 x accuracy/K
 |
| 13.1.8 Safety |
 Insulation: Class 2; Pollution: 2; Over-voltage category: CAT III 600V~ (Phase-phase; CAT II 1000V~ (Phase-Phase)
 |
| Mechanical Features: |
 Dimensions: 8.9” (L) x 4.1” (W) x 2.1” (H)
225(L) x 104(W) x 54(H) mm
 |
| Weight: |
 3.3 Lb (1.5kg)
 |
| Internal Power Supply: |
 8 batteries 1.5V series AA
 |
| Battery Life: |
 3-hours
 |
| External Power Supply: |
 Use only Amprobe power supply
Adapter code DM4EXTPS
 |
| Sampling Speed: |
 83.33 usec at 60Hz.
 |
| No. of Samples Per Period: |
 128
 |
| Clamp: |
 Opening: 2.15” (53 mm); Maximum Diameter of The Cable: 2.00” (50 mm)
 |
| Environment Operating Conditions: |
 Reference Temperature: 73°F ± 2°F (23°C ± 1°C)
 |
| |
 Operating Temperature: 32°F to 122°F (0°C to 50 °C)
 |
| |
 Relative Humidity: <70%
 |
| |
 Storage Temperature: 14°F to 140°F (-10°C to 60 °C)
 |
| |
 Storage Humidity: <80%
 |
| Amprobe DM-4 Power Quality Recorder Analyzer Accessories Optional: |
| 100A Compact Clamp (0.5A to 100A): |
 Part Number: DM-CT-100
 |
| USB-RS-232 Adapter: |
 Part Number: RS-USB
 |
| Remote user interface protective case: |
 Part Number: DM-4CASE
 |
| Optional test lead accessories: |
 MTL-90B, MTL-100 Series (100 to
106), MTL-500, MTL-501 and VRC-320
 |
| Amprobe DM-4 Power Quality Recorder Analyzer Characteristics: |
| Replacement Parts supplied with product: |

 |
| 1000A Clamp: |
 Part Number: DM-CT-HTA
 |
| Remote user interface (PDA) with connection cables |
 Part Number: Recommended Tungsten E2
ordered through PALM retailers, visit palm.com for details
 |
| Soft Carrying case: |
 Part Number:HW1254A
 |
| External power supply 12VDC: |
 DMT-EXTPS
 |
| Test leads and alligator clips (set of 4): |
 Part Number: KITENERGY3
 |
| PDA/DM-4 Interface Cable: |
 Part Number: RS-PDA
 |
| RS-232 Computer Cable: |
 Part Number: RS-232
 |
| |
 PC Windows Software
 |
| |
 Palm OS Software
 |
| |
 Instruction Manual
 |

Need Technical Advise? Please Call: 602-795-4033
Browse Similar Products |