Datasheet: 8230-AEMC |
 |
| AEMC 8230 Single-Phase Power Quality Analyzer Description: |
 AEMC 8230 Single-Phase Power Quality Analyzer is a single-phase power quality analyzer that is easy-to-use, compact and shock-resistant. It is intended for technicians and engineers to measure and carry out diagnostic work and power quality work on single- or three-phase balanced load networks.

Users are able to obtain instant waveforms of an electrical network’s principal characteristics, and also monitor their variation over a period of time.

The multi-tasking measurement system simultaneously handles all the measurement functions and waveform display of the various magnitudes, detection, continuous recordings and their display without any constraints.
 |
| AEMC 8230 Single-Phase Power Quality Analyzer Applications: |
| |
 Motor start-up analysis
 |
| |
 Verification of power distribution circuits
 |
| |
 Measurement and recording of power system quality (kW, VA, VAR)
 |
| |
 Energy metering (kVAh, VARh, kWh)
 |
| |
 In-plant troubleshooting of power distribution panels and individual machinery
 |
| |
 Determine harmonic problems originating from source or load
 |
| AEMC 8230 Single-Phase Power Quality Analyzer Characteristics: |
| |
 Measures up to 660Vrms or VDC
 |
| |
 Measures up to 6500AAC or 1400ADC (probe dependent)
 |
| |
 Displays Min, Max and Average Volts and Amps, Crest Factor, Peak value and K-Factor
 |
| |
 Calculates and displays Watts, VARs and VA, Power Factor and Displacement Power Factor for single-phase and balanced three-phase
 |
| |
 Displays total harmonic distortion (THD-F and THD-R) for voltage and current
 |
| |
 Displays individual harmonic values and % for Volts and Amps through the 50th harmonic
 |
| |
 Captures, displays and stores inrush current waveforms and statistics
 |
| |
 Stores up to eight screen captures
 |
| |
 Stores up to 1MB of trend recorded data
 |
| |
 Configurable from DataView® software or front panel
 |
| |
 Download stored data to DataView® software via optical with isolated USB port
 |
| |
 Captures up to 4096 alarm events using up to 10 different thresholds
 |
| |
 Displays and records up to 17 different power quality parameters
 |
| |
 Includes DataView® software FREE
 |
| AEMC 8230 Single-Phase Power Quality Analyzer Specifications: |
| Electrical Specifications: |

 |
| Voltage (TRMS) |
 Phase-to-Phase: 660V
Phase-to-Neutral: 600V
 |
| Current (TRMS) |
 MN Clamp: 5mA to 100mA/120A or 2 to 240A
MR Clamp: 10 to 1000Aac, 10 to 1400Adc
SR Clamp: 3 to 1200A
AmpFlex: 10 to 6500A
 |
| Frequency (Hz) |
 40 to 70Hz
 |
| Other Measurements |
 KW, kVAR, PF, DPF, kWh, kVARh, kVAh, K-Factor, Flicker, Harmonic Phase Shift, Phase Rotation
 |
| Harmonics THD-R, THD-F, V, A, VA |
 1st to 50th, Direction, Sequence
 |
| Sampling Frequency |
 256 Samples/cycle
 |
| Data Storage |
 1.5MB partitioned for waveforms, alarms, and trend recording
 |
| Power Source |
 Six NiMH AA rechargeable battery pack
AC Supply: 120/230Vac (50/60Hz)
 |
| Battery Life |
 ≥ 8 hours with display on
≥ 40 hours with display off (recording mode)
 |
| Mechanical Specifications: |

 |
| Communication Port |
 Optically isolated USB
 |
| Display |
 1/4 VGA (320 x 240) color LCD
 |
| Dimensions |
 8.3 x 4.3 x 2.4 in (211 x 108 x 60 mm)
 |
| Weight |
 1.9 lbs (0.88kg)
 |
| Safety Rating |
 EN 61010, 600V Cat. III, IP 54, Pollution Degree 2
 |

Need Technical Advise? Please Call: 602-795-4033
Browse Similar Products |