Datasheet: 8230-SR193-BK-AEMC |
 |
| AEMC 8230 SR193-BK Single-Phase Power Quality Analyzer Description: |
 AEMC 8230 SR193-BK Single-Phase Power Quality Analyzer is easy-to-use, compact and shock-resistant. It is intended for technicians and engineers to measure and carry out diagnostic work and power quality work on single- or three-phase balanced load networks. Users are able to obtain instant waveforms of an electrical network’s principal characteristics, and also monitor their variation over a period of time.Â

The multi-tasking measurement system simultaneously handles all the measurement functions and waveform display of the various magnitudes, detection, continuous recordings and their display without any constraints.

The PowerPad Jr. Model 8230 with MN93 is supplied with a black 1200A current probe.
 |
| AEMC 8230 SR193-BK Single-Phase Power Quality Analyzer Applications: |
| |
 Motor start-up analysis
 |
| |
 Verification of power distribution circuits
 |
| |
 Measurement and recording of power system quality (kW, VA, VAR)
 |
| |
 Energy metering (kVAh, VARh, kWh)
 |
| |
 In-plant troubleshooting of power distribution panels and individual machinery
 |
| |
 Determine harmonic problems originating from source or load
 |
| AEMC 8230 SR193-BK Single-Phase Power Quality Analyzer Characteristics: |
| |
 Measures up to 660Vrms or VDC
 |
| |
 Measures up to 6500AAC or 1400ADC (probe dependent)
 |
| |
 Displays Min, Max and Average Volts and Amps, Crest Factor, Peak value and K-Factor
 |
| |
 Calculates and displays Watts, VARs and VA, Power Factor and Displacement Power Factor for single-phase and balanced three-phase
 |
| |
 Displays total harmonic distortion (THD-F and THD-R) for voltage and current
 |
| |
 Displays individual harmonic values and % for Volts and Amps through the 50th harmonic
 |
| |
 Captures, displays and stores inrush current waveforms and statistics
 |
| |
 Stores up to eight screen captures
 |
| |
 Stores up to 1MB of trend recorded data
 |
| |
 Configurable from DataView® software or front panel
 |
| |
 Download stored data to DataView® software via optical with isolated USB port
 |
| |
 Captures up to 4096 alarm events using up to 10 different thresholds
 |
| |
 Displays and records up to 17 different power quality parameters
 |
| |
 Includes DataView® software FREE
 |
| AEMC 8230 SR193-BK Single-Phase Power Quality Analyzer Specifications: |
| Voltage (TRMS) |
 Phase-to-Phase: 660V
Phase-to-Neutral: 600V
 |
| Current (TRMS) |
 MN Clamp: 5mA to 100mA/120A or 2 to 240A
MR Clamp: 10 to 1000Aac, 10 to 1400Adc
SR Clamp: 3 to 1200A
AmpFlex: 10 to 6500A
 |
| Frequency (Hz) |
 40 to 70Hz
 |
| Other Measurements |
 KW, kVAR, PF, DPF, kWh, kVARh, kVAh, K-Factor, Flicker, Harmonic Phase Shift, Phase Rotation
 |
| Harmonics THD-R, THD-F, V, A, VA |
 1st to 50th, Direction, Sequence
 |
| Sampling Frequency |
 256 Samples/cycle
 |
| Data Storage |
 1.5MB partitioned for waveforms, alarms, and trend recording
 |
| Power Source |
 Six NiMH AA rechargeable battery pack
AC Supply: 120/230Vac (50/60Hz)
 |
| Battery Life |
 ≥ 8 hours with display on
≥ 40 hours with display off (recording mode)
 |
| Communication Port: |
 Optically isolated USB
 |
| Dimensions: |
 8.3 x 4.3 x 2.4 in (211 x 108 x 60 mm)
 |
| Display: |
 1/4 VGA (320 x 240) color LCD
 |
| Safety Rating: |
 EN 61010, 600V Cat. III, IP 54, Pollution Degree 2
 |
| Weight: |
 1.9 lbs (0.88kg)
 |

Need Technical Advise? Please Call: 602-795-4033
Browse Similar Products |